ANSI CLASS |
With long stud |
57-1L |
57-2L |
57-3L |
57-4L |
57-5L |
With short stud |
57-1S |
57-2S |
57-3S |
57-4S |
57-5S |
|
Fig. No. |
1 |
2 |
3 |
4 |
5 |
|
Creepage Distance (mm) |
356 |
559 |
737 |
1016 |
1143 |
|
Dry Arcing Distance (mm) |
165 |
241 |
311 |
368 |
430 |
|
Cantilever Strength(kN) |
12.5 |
12.5 |
12.5 |
12.5 |
12.5 |
|
Power Frequency Flashover Voltage |
Dry /kV |
70 |
100 |
125 |
140 |
160 |
Wet/kV |
50 |
70 |
95 |
110 |
130 |
|
Critical Impulse Flashover Voltage |
Positive/kV |
120 |
160 |
200 |
230 |
265 |
Negative/kV |
155 |
205 |
260 |
340 |
380 |
|
Radio Influence voltage |
Test Voltage to ground/kV |
15 |
22 |
30 |
44 |
44 |
Maximum RIV at 1MHz/uV |
100 |
100 |
200 |
200 |
200 |